1001A-WPS-CI-YZ-TM-ECK - Encl Purge Sys, 1001A, With Pressure Switch, Class I, Top Mnt
Item# 1001A-WPS-CI-YZ-TM-ECK - Encl Purge Sys, 1001A, With Pressure Switch, Class I, Top Mnt
1001A Series Information
- Optional Alarm Output Indicated Air Lock Failure
- NFPA 70, NFPA 496, ISA 12.4 Standards
Model 1001A is an enclosure pressurization or purging system that operates on a supply of compressed instrument air or inert gas. It regulates and monitors pressure within sealed (protected) enclosure(s), in order to prevent combustible dust accumulation or remove and prevent flammable gas or vapor accumulations. In Class II areas, the system maintains a "safe" (1.0") pressure. In Class I areas, the system accomplishes four air exchanges and maintains a "safe" (0.25") pressure. These processes reduce the hazardous (classified) area rating within the enclosure(s), in accordance with the NEC ‑ NFPA 70, Article 500, NFPA 496 and ISA 12.4.